MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Ceiling panels in car are open egg crate type and provide no protection in event of breakage. Replace with plastic tubes over bulbs.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Unit has oil recovery pump in pit, which is for temporary use only. Measurement of oil cannot be obtained.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Ceiling panels in car are open egg crate type and provide no protection in the event of breakage. Replace panels with plastic tubes over bulbs.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
Need to perform OSV testing. Re-inspection required
|
12/29/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
12/28/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Fireman's recall stop switch did not stop work on recall while descending. 14 days to repair. Did not Red Tag.
|
8/19/2020
|