Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Ceiling panels in car are open egg crate type and provide no protection in event of breakage. Replace with plastic tubes over bulbs. 1/27/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Ceiling panels in car are open egg crate type and provide no protection in the event of breakage. Replace panels with plastic tubes over bulbs. 1/27/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 12/28/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fireman's recall stop switch did not stop work on recall while descending. 14 days to repair. Did not Red Tag. 8/19/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Elevator car door restrictor does not work, needs repaired. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Need to perform OSV testing. Re-inspection required 12/29/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Unit has oil recovery pump in pit, which is for temporary use only. Measurement of oil cannot be obtained. 1/27/2026