Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone did not work, phone line was dead 8/16/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) The Maintenance Control Program On-Site documents are not in the machine room.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation the monthly fire service test log is missing
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(1) the oil record log is missing
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x the emergency light battery is dead, replace battery 6/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals replace the packing on the jack, it is leaking and overfilling the collection bucket in the pit between Maintenance visits
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits clean up oil on the pit floor and remove oil soaked rags
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x replace emergency phone, phone line tested active, the phone in the elevator is dead and needs replaced 5/29/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current copy of the state operating certificate in the machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Post monthly fire service test log in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide access to the complete MCP in the machine room according to 8.6
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine room fire extinguisher inspection tag expired
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace packing on jack that is leaking significantly
MO Minimum : Elevators (I) - Pits (I)1 Clean up oil on pit floor and remove oil soaked rags
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys x Replace Phase I key switch due to intermittent issues