Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair the emergency phone. 8/12/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Replace packing on jack that is leaking significantly 6/12/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Clean up oil on pit floor and remove oil soaked rags 6/12/2026
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys Yes No Replace Phase I key switch due to intermittent issues 6/6/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emergency phone did not work, phone line was dead 8/16/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current copy of the state operating certificate in the machine room 6/12/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019 6/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No replace emergency phone, phone line tested active, the phone in the elevator is dead and needs replaced 5/29/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) No No The Maintenance Control Program On-Site documents are not in the machine room. 6/12/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide access to the complete MCP in the machine room according to 8.6 6/12/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(1) No No the oil record log is missing 6/12/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine room fire extinguisher inspection tag expired 6/12/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No the monthly fire service test log is missing 6/12/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Post monthly fire service test log in the machine room 6/12/2026
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) Yes No the emergency light battery is dead, replace battery 6/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No clean up oil on the pit floor and remove oil soaked rags 6/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals No No replace the packing on the jack, it is leaking and overfilling the collection bucket in the pit between Maintenance visits 6/12/2026