MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
open egg crate ceiling panels, the light tubes shall be guarded
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)4
|
|
|
does not have crosshead data tag
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)6
|
|
|
the hydraulic tank is not marked #4
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
do not store non elevator related material in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
the pit bucket was overflowing in the pit
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
clean up oil and water mixture on the pit floor
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
elevator has an open egg crate drop ceiling panels, light tubes shall be guarded to prevent breakage
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
do not store non-elevator related material in the machine room
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
escape hatch is not secured from opening from inside the elevator
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
does not have a crosshead data tag, provide a crosshead data tag
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
|
|
the fire service phase 1 audible signal in the car operating panel did not work
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
the alarm bell did not work on battery power
|
7/12/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
the emergency phone did not work, no dial tone
|
7/12/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
the emergency lights did not come on, the alarm bell worked
|
8/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone did not work
|
8/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
emergency lights and bell did not work, replace battery so that the emergency lights and bell work when the 110 volt power is off.
|
6/21/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone says that it doesn't have emergency number programmed
|
6/21/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
adjust the door restrictor, the hook did not catch
|
6/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
the emergency light battery is dead, replace the emergency light battery
|
6/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone has not been programmed with the phone number to call, program the emergency phone
|
6/5/2024
|