MO Minimum : Elevators (H) - Machine Rooms (H)4 do not store non-elevator related material in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x the alarm bell did not work on battery power 7/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x the emergency phone did not work, no dial tone 7/12/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting open egg crate ceiling panels, the light tubes shall be guarded
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 does not have crosshead data tag
MO Minimum : Elevators (H) - Machine Rooms (H)6 the hydraulic tank is not marked #4
MO Minimum : Elevators (H) - Machine Rooms (H)4 do not store non elevator related material in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x the emergency lights did not come on, the alarm bell worked 8/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The emergency phone did not work 8/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection the pit bucket was overflowing in the pit
MO Minimum : Elevators (I) - Pits (I)1 clean up oil and water mixture on the pit floor
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting elevator has an open egg crate drop ceiling panels, light tubes shall be guarded to prevent breakage
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x emergency lights and bell did not work, replace battery so that the emergency lights and bell work when the 110 volt power is off. 6/21/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone says that it doesn't have emergency number programmed 6/21/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 escape hatch is not secured from opening from inside the elevator
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x adjust the door restrictor, the hook did not catch 6/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates does not have a crosshead data tag, provide a crosshead data tag
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal the fire service phase 1 audible signal in the car operating panel did not work
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x the emergency light battery is dead, replace the emergency light battery 6/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone has not been programmed with the phone number to call, program the emergency phone 6/5/2024