Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post Phase I instructions near f/f switch in lobby.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not work on 110v emergency power. Repair or replace light 7/18/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work on emergency or normal power. Repair or replace phone 7/18/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone in car not working 6/8/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be provided on site for each elevator.
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 7/28/2022
conversion conversion conversion - reinspect x Emergency phone in car not working 11/9/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.