Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site. 10/23/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Ceiling panels in car are open egg crate type, which do not provide protection for passengers in event of light bulb breakage. Panels should be replaced with solid type or have plastic tubes with endcaps installed over bulbs or replace fixture with LED fixture 10/23/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 10/23/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency battery lowering device is not working. Re-inspection required 8/19/2024