ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
12/28/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.13 - Emergency exit
|
2.14.1.5
|
|
|
Top emergency exit shall be properly secured. Currently bolted closed, not with thumb-screws, requiring tools to open.
|
12/1/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.13 - Emergency exit
|
2.14.1.5
|
|
|
Top Emergency exit shall be properly secure, currently bolted closed, not with thumb-screws requiring tools to open
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
3.26.10 (Auxiliary Power)(Re-Inspection)
|
x
|
|
Battery Lowering shall work
|
12/11/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
3.26.10 (Auxiliary Power)(Re-Inspection)
|
x
|
|
The auxiliary power lowering operation shall be functional.
|
1/6/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
11/6/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
3.26.10 (Auxiliary Power)(Re-Inspection)
|
x
|
|
Battery lowering shall work. Repair or replace.
|
12/1/2025
|