A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-1996 : Elevators
|
2.37 - Pressure Switch
|
306.14
|
x
|
|
There is no pressure switch. When cylinders are installed with the top of the cylinder above the top of the storage tank, a pressure switch shall be provided in the line between the cylinder and the valve, which shall be activated by the loss of positive pressure at the top of the cylinder.
|
|
A17.1-1996 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
102
|
x
|
|
102.2(c)(1) - Sprinklers pipes shall not run the entire hoistway. Customer may apply for a variance.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone shall work. There is no phone line.
|
|
A17.1-1996 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
102
|
x
|
|
102.2(c)(2) - Sprinkler branch lines in the hoistway shall supply sprinklers at not more than 1 floor level. Customer may apply for a variance.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
5/12/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Up-to-date operating certificate is required in the machine room.
|
5/12/2023
|