Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 x 102.2(c)(1) - Sprinklers pipes shall not run the entire hoistway. Customer may apply for a variance. 4/25/2025
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 x 102.2(c)(2) - Sprinkler branch lines in the hoistway shall supply sprinklers at not more than 1 floor level. Customer may apply for a variance. 4/25/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/21/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/21/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone shall work. There is no phone line. 4/25/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 5/12/2023
A17.1-1996 : Elevators 2.37 - Pressure Switch 306.14 x There is no pressure switch. When cylinders are installed with the top of the cylinder above the top of the storage tank, a pressure switch shall be provided in the line between the cylinder and the valve, which shall be activated by the loss of positive pressure at the top of the cylinder. 4/25/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up-to-date operating certificate is required in the machine room. 5/12/2023