MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current copy of the state operating certificate in the machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Post monthly fire service test log in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide access to the complete MCP in the machine room according to 8.6
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019
|
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
replace first floor hoistway door astragal, it is no longer glued to the bottom half of the door
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
clean up the oil on the pit floor
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
repair machine room air conditioner so it works
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Repair and adjust door restrictor, it is not working
|
8/30/2024
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
8.11.3.1.1(h)
|
x
|
|
adjust the door close force to below 30 lbs, the doors maxed out my gauge (2.13.4.2.3)
|
6/16/2023
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
repair and adjusted door restrictor, it is not working
|
6/3/2024
|