Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide access to the complete MCP in the machine room according to 8.6
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x repair and adjust door restrictor, it is not working 6/3/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Post monthly fire service test log in the machine room
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Repair and adjust door restrictor, it is not working 8/30/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x emergency lights did not come on, suspect that the emergency light battery is dead, replace battery 6/16/2023
A17.1-2016 : Elevators 1.8 - Door closing force 8.11.3.1.1(h) x the door close force is right at the maximum, recommend adjusting it so the force is below 30 lbf. (A17.1-2016 [2.13.4.2.3]) force shall not exceed 30 lbf 6/16/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x elevator shutdown during the inspection, test was not completed, need to schedule reinspection 8/16/2021
A17.1-2016 : Elevators 2.39 - Low Oil Protection 8.6.5.12 low on oil, cavitates at the top landing (A17.1-2016 [3.24.2]) adequate liquid reserve in order to prevent the entrance of air into the system.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current copy of the state operating certificate in the machine room