MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
elevator shutdown during the inspection, test was not completed, need to schedule reinspection
|
8/16/2021
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
emergency lights did not come on, suspect that the emergency light battery is dead, replace battery
|
6/16/2023
|
A17.1-2016 : Elevators
|
2.39 - Low Oil Protection
|
8.6.5.12
|
|
|
low on oil, cavitates at the top landing (A17.1-2016 [3.24.2]) adequate liquid reserve in order to prevent the entrance of air into the system.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current copy of the state operating certificate in the machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Post monthly fire service test log in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide access to the complete MCP in the machine room according to 8.6
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
repair and adjust door restrictor, it is not working
|
6/3/2024
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Repair and adjust door restrictor, it is not working
|
8/30/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019
|
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
8.11.3.1.1(h)
|
x
|
|
the door close force is right at the maximum, recommend adjusting it so the force is below 30 lbf. (A17.1-2016 [2.13.4.2.3]) force shall not exceed 30 lbf
|
6/16/2023
|