ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.2 - Stop switches
|
2.26.2.5
|
x
|
|
Stop switch shall be wired to alarm for audible notification.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room door shall be self-closing and self-locking.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
Machine room lighting shall be 10 ftc at the floor.
|
12/6/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
|
|
Gutter and/or guard overhead pipes.
|
12/6/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
12/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher is out of date. A current tested, ABC type fire extinguisher shall be provided in the machine room.
|
10/28/2021
|
conversion
|
conversion
|
n/a
|
|
|
Fire extinguisher is out of date.
|
12/6/2018
|
conversion
|
conversion
|
n/a
|
|
|
Machine room door shall be self-locking and self-closing.
|
12/6/2018
|
conversion
|
conversion
|
n/a
|
|
|
All pipes above or in close proximity of the elevator equipment shall be guarded or guttered.
|
12/6/2018
|
conversion
|
conversion
|
n/a
|
|
|
Lighting in the machine room shall be 10 foot candles at the floor.
|
12/6/2018
|
conversion
|
conversion
|
n/a
|
|
|
Machine room shall be cleaned of all materials and equipment not necessary for the maintenance and operation of the elevator.
|
12/6/2018
|