Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Test and log firefighter operation monthly 11/17/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(4) No No Post emergency evacuation of passengers procedure inside machine room 11/17/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Test operation of elevator on emergency power with an inspector present 12/8/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No Emergency light does not operate 12/8/2021
A17.1-1996 : Elevators 1.8 - Door closing force 1001.2(a)(8) Yes No Door pressure exceeds 30# 12/8/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency bell does not operate 12/8/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys No No Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operated by the same key 10/24/2022
A17.1-2016 : Elevators 1.8 - Door closing force 8.6.4.19.8 Yes No Door force exceeds 30# 11/29/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Test operation of elevator on emergency power 11/29/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes Yes In car firefighter keyswitch does not disable car calls or door close operation when keyed to the HOLD position 11/29/2022
A17.1-2016 : Elevators 1.8 - Door closing force 8.6.4.19.8 Yes No Door force exceeds 30# 10/24/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Test emergency power operation 12/13/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 1/5/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No MRL not up to date 2/1/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 2/1/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No The emergency power was not tested. 11/13/2024