A17.1-1996 : Elevators
|
1.8 - Door closing force
|
1001.2(a)(8)
|
x
|
|
Door pressure exceeds 30#
|
12/8/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light does not operate
|
12/8/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell does not operate
|
12/8/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
|
|
Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operated by the same key
|
10/24/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
In car firefighter keyswitch does not disable car calls or door close operation when keyed to the HOLD position
|
11/29/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
2/1/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
1/5/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
The emergency power was not tested.
|
11/13/2024
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
8.6.4.19.8
|
x
|
|
Door force exceeds 30#
|
10/24/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test emergency power operation
|
12/13/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Test and log firefighter operation monthly
|
11/17/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(4)
|
|
|
Post emergency evacuation of passengers procedure inside machine room
|
11/17/2020
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
8.6.4.19.8
|
x
|
|
Door force exceeds 30#
|
11/29/2022
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test operation of elevator on emergency power
|
11/29/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
MRL not up to date
|
2/1/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test operation of elevator on emergency power with an inspector present
|
12/8/2021
|