Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.8 - Door closing force 1001.2(a)(8) x Door pressure exceeds 30# 12/8/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal x No audible signal during phase 1 recall 10/24/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal x No audible signal during fire recall 12/13/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal x no audible signal on fire recall 1/4/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys Install FEO-K1 keyswitch. All elevators in the same building shall have firefighter keyswitches operable by the same key 10/24/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 1/5/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) MRL not up to date 2/1/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly 11/17/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace cylinder on fire recall keyswitch. The cylinder turns past the on position. 1/5/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency power was not tested. 11/13/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test operation of elevator on emergency power 10/24/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency power operation 12/13/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test operation of elevator on emergency power with an inspector present 12/8/2021
A17.1-2016 : Elevators 1.8 - Door closing force 8.6.4.19.8 x Door force exceeds 30# 10/24/2023