Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational with 24/7 support. 11/4/2020
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting The machine room lights shall be repaired. 3/15/2024
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting The machine room lights shall be guarded. 3/15/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 3/15/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 2/27/2024
A17.1-1996 : Elevators 2.14 - Code data plate 215 The code data plate required by A17.1 2013, 2016 8.9 shall be provided in plain view, securely attached to each main line disconnect or controller. 3/15/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/15/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a copy of the current state operating certificate. 3/15/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 11/21/2018
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x The in-car stop switch shall not be rendered inoperative on phase one fire service until the car is in motion. 2/27/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase II fire service shall be operational. 14 days to correct violation or unit will be red tagged and locked out of service. 12/19/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 3/15/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/15/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 The data on the MCP shall be filled out as required by A17.1 2016 8.6.1.4.1(a)(3). 3/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fire service phase one key-switch bezel shall be legible. 3/15/2024
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 3/15/2024
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x The overspeed valve is not sealed and has been previously cited that a category 5 test is needed. A category 5 test shall be performed within 90 days. 2/27/2024
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x A category 5 test of the overspeed valve shall be performed within 90 days. 3/15/2024