conversion
|
conversion
|
n/a
|
|
|
Remove standing water on machine room floor. AC unit in machine room leaking water onto floor.
|
1/9/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
8.11.2.1.2(o)
|
x
|
|
Provide means for ascending car and unintended movement protection. Existing rope gripper does not function correctly.
|
4/18/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
emg. lt. an bell not working phone works but is the wrong kind
|
5/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency light does not illuminate
|
5/24/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell does not operate
|
5/24/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
All elevators in the same building shall have firefighter keyswitches operated by the same key
|
5/24/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone button on car operating panel does not activate the phone
|
9/6/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection)
|
x
|
|
car firefighter operation panel needs to have a lockable cover
|
9/6/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit covered in water
|
1/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
8.6.1.6.3
|
|
|
Interior of controller and its components need to be cleaned of coal dust
|
1/1/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
incomplete MCP
|
1/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Layer of coal dust covering entire machine room and equipment needs to be removed
|
1/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
machine room air conditioner does not work
|
1/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
hoistway access switches do not function.
|
1/1/2024
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
hoistway access sws. not working
|
1/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current state operating certificate not displayed
|
1/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
1/24/2024
|