Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 5/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone button on car operating panel does not activate emergency phone. 9/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 1/24/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(o) x Rope gripper does not function. Need to provide means for ascending car and unintended motion protection. 9/4/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No maintenance control plan in machine room 1/1/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No up to date maintenance records in machine room 1/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers procedure in machine room 3/3/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 machine room air conditioner does not function. 1/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) x install fire hat jewel in firefighter operation panel. 9/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x car firefighter operation panel shall have a locked cover. 9/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Test and log firefighter operation monthly 3/3/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) x All elevators in the same building shall use the same key for firefighter operation 5/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x Fire hat jewel needs to be installed on firefighter cabinet panel 5/25/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) x All elevators in the same building shall have firefighter keyswitches operated by the same key 5/25/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current state operating certificate displayed 1/1/2024