Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a new copy of the state operating certificate is to be posted in the machine room every year
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.29 - Car and counterweight safeties Table 2.17.3 x x according to table maximum stopping distance is 16 inches measured 18 inches, make adjustments and retest stopping distance 7/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone did not work, call could not be completed as dialed 4/26/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current copy of the State Operating Certificate in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post instructions for viewing on-site the records for the Maintenance Control Program (MCP)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Post monthly fire service test log in the machine room
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing the monthly fire service test log is to be available in the machine room