Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits Clean the pit. 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 2.26.1.1 The door open button in COP and hall call button at 3rd floor are missing and shall be replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 10/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. Repeat violation
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Provide lobby warning placards on all elevator entrances. 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 Spaces containing machines, control equipment, sheaves, and other machinery shall be separated from the remainder of the building by a fire resistive enclosure. The large openings in the machine room ceiling shall be repaired.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door shall be self-locking and self-closing. Repeat violation.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 All machine rooms or enclosures shall have a self-locking door and shall be operable from the interior space without use of a key. 10/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Battery lowering shall work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) Replace the missing "Up" botton at 2nd floor lobby. (Currently an open hole) 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) Post " In Case of Fire" signage at each hall station. 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 8.11.2.1.2(d) Black mold is observed on machine room wall, below the controller. Remove the mold. 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) Clean the car top. 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Provide a code compliant fire extinguisher in the machine room. 10/24/2019
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) Debris shall be removed from the pit. The pit shall be kept clean and dry. 8/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 11/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 10/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Oil usage, findings for firefighters' service operation tests, and other records, along with instructions for locating such records shall be posted as required by A17.2, Item 2.41 8/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide MCP. 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation shall be provided in the machine room. Logs from 2022 - 2025 missing.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.1.7 8.6.1.7.5 - Emergency lowering shall be operational. 8/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 10/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing A fire service testing log shall be kept on-site. 10/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Fire service testing shall be documented monthly on log sheet.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Main line disconnect has a note taped to it stating, "do not run on inspection, blows fuse F7". Investigate and repair as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Car slide guides are very worn and shall be replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit shall be kept clean. Clean the pit of oil, dirt, and debris. Repeat violation.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the pit of oil, dirt, and debris. 10/10/2022