A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell inoperable and shall be repaired or replaced.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car shall work on backup power. Re-inspection required
|
12/12/2023
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
In firefighters emergency operation, phase II, unit unable to access floors above 3, possible due to security card reader issue. Did not red-tag, as all units at this location have the same issue. Repair, Re-inspection required
|
12/12/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Light in pit is not working
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Lights in the pit are not working
|
|
A17.1-1996 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.4.10.1.2 - Protection not functioning
|
x
|
|
Repair broken ground wire on cut derailment device.
|
2/18/2020
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Repair car door restrictor.
|
11/10/2020
|
A17.1-1996 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.4.10.1.2 - Protection not functioning
|
x
|
|
Seismic did not work when wires were grounded on counterweight mounted grounding device. Reinspect In 30 days
|
1/31/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written maintenance control program shall be provided on site for each elevator.
|
4/6/2021
|