MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x elev has sprinkler in machroom but has no heat detector or shunt trip or smoke detector
MO Minimum : Elevators (H) - Machine Rooms (H)2 machroom door lock is defeatable
MO Minimum : Elevators (H) - Machine Rooms (H)2 machroom door lock is defeatable
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone wouldnt dial out 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide an updated fire extingusher in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair the emergency phone. 11/3/2023
MO Minimum : Elevators (I) - Pits (I)8 sump pump hole needs a fire proof cover over it instead of wooden one current over it now