MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Repair roof hatch door. Latch arm broken
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Electrical box cover(octagonal) missing in hoistway, top floor.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
40-5.100 needs current certificate posted
|
3/31/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5yr test incomplete, weights failed to arrive. Must return for weight/Gov test.
|
8/13/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
1.18.1/8.11.2.1.1(r) Car Door restrictor shall work. (REINSPECTION REQUIRED)
|
8/13/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5yr test incomplete, weights failed to arrive. Must return for weight/Gov test.
|
8/13/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
1.18.1/8.11.2.1.1(r) Car Door restrictor shall work. (REINSPECTION REQUIRED)
|
8/13/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
I(1)/5.1/8.11.2.1.5(a) : Excessive debris in pit.
|
8/16/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace missing Phase 1 signage.
|
8/16/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work and give proper location. DIALS 911. Unresponsive. Reprogram to non-emergency number
|
11/18/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
Jumper on DRV board for drive machine thermosistor.
|
11/18/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide operational telephone in elevator cab
|
7/3/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide operational telephone in elevator cab
|
7/21/2023
|