MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)1
|
|
|
Replace missing car hand rail.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean car top.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Clean down hoistway.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Clean the pit.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)4
|
|
|
Pit ladder is UNSAFE. Repair or replace.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Seal penetrations in hoistway from basement demolition. Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height
|
8/16/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Hole in pit must be fully enclosed
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean & dry
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Pit ladder must be fixed or replaced
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Bulbs and tubes shall be guarded to prevent breakage
|
8/16/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Provide Phase II Fire Service Instructions on Car Operating Panel
|
8/16/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Hoistway walls damaged (water) drywall missing. Replace.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Provide machine room door to be self closing and self locking.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide car speed adjusted to contract speed. Currently running 165-170 rpm.
|
|
A17.1-1996 : Elevators
|
5.4 - Normal terminal stopping devices
|
1002.2e
|
x
|
|
While on car top inspection, car ran past directional and onto final. Adjust as needed.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Door restrictor is inoperable. When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening
|
1/5/2024
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Car emergency light, only one bulb working-two required.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Phone in car fails to establish two-way communication
|
1/5/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work. Re-inspection required
|
7/1/2025
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work properly.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|