Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone in car fails to establish two-way communication 1/5/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. Re-inspection required 7/1/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Door restrictor is inoperable. When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening 1/5/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work properly.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Hoistway door, 7th floor, bottom door guide missing screw dragging sill. Repair as needed.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No Car emergency light, only one bulb working-two required.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Provide car speed adjusted to contract speed. Currently running 165-170 rpm.
A17.1-1996 : Elevators 5.4 - Normal terminal stopping devices 1002.2e Yes No While on car top inspection, car ran past directional and onto final. Adjust as needed.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Provide machine room door to be self closing and self locking.
MO Minimum : Elevators (A) - Hoistways (A)13 No No Hoistway walls damaged (water) drywall missing. Replace.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Bulbs and tubes shall be guarded to prevent breakage 8/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Provide Phase II Fire Service Instructions on Car Operating Panel 8/16/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 No No Replace missing car hand rail.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean car top.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Clean down hoistway.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Clean the pit.
MO Minimum : Elevators (I) - Pits (I)4 No No Pit ladder is UNSAFE. Repair or replace.
MO Minimum : Elevators (A) - Hoistways (A)13 No No Seal penetrations in hoistway from basement demolition. Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height 8/16/2023
MO Minimum : Elevators (A) - Hoistways (A)13 No No Hole in pit must be fully enclosed
MO Minimum : Elevators (I) - Pits (I)1 No No Pit shall be kept clean & dry
MO Minimum : Elevators (I) - Pits (I)5 No No Pit ladder must be fixed or replaced
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room