MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
New floor opening/door added. Install missing flooring in front of first floor door.
|
4/24/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
New floor opening/door added. Smoke detector added at first floor must be tested/accepted.
|
4/24/2024
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
100
|
x
|
|
New floor opening/door added. Repair fire penetrations on all edges of new door frame on both sides.
|
4/24/2024
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
x
|
|
New floor opening/door added. Missing secondary fire retainer on left door.
|
4/24/2024
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
A current ABC type fire extinguisher shall be provided in the machine room.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
New floor opening/door added. Repair fire penetrations on first floor wall below call buttons and PI.
|
4/24/2024
|