Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)13 Hoistway shall be of solid construction. Repair opening on hoistway at bottom landing along vertical column to right of door jamb. 1/25/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Emergency power hall jewel(s) shall illuminate when emergency power is activated (jewels on lobby planel on level 491 and riser on level 532).
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) x Fire Service keyswitch at main fire floor funcitons properly. Additional Fire Service keyswitch on Lobby Panel does not activate Ph I.