A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
x
|
|
Fire Service keyswitch at main fire floor funcitons properly. Additional Fire Service keyswitch on Lobby Panel does not activate Ph I.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
|
|
Emergency power hall jewel(s) shall illuminate when emergency power is activated (jewels on lobby planel on level 491 and riser on level 532).
|
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Hoistway shall be of solid construction. Repair opening on hoistway at bottom landing along vertical column to right of door jamb.
|
1/25/2021
|