Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.2 Minimum Illumination Cab lighting - all lamps shall work. 4/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 2.16.3.1 Capacity Plates Car operating panel shall have car capacity displayed. 4/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Car operating panel shall have car number displayed. 4/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean car top. 3/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean the pit. 3/16/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. 4/12/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 Hoist ropes are showing moderate "rouge". Ropes shall be cleaned and lubricated per OEM recommendations. Monitor condition and diameter. 4/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. The lock is damaged. 4/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Provide machine room door to be self-locking type. 8/13/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.40 - Maintenance Records 2.26.1.4 Inspection Operation Provide maintenance control program. 8/13/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Replace broken Phase I visual indicator, retest for operation. Provide working audible indicator upon activation of Phase I operation. Retest 4/17/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Replace missing/damaged emergency power jewel in hall station. 4/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean. Remove excess debris. 4/15/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The test is incomplete due to shutdown of elevator #2 during test. Remaining items to test: light, bell, phone, buffers, governor switch/jaw, governor PO/PT, unintended motion up/down. All weight portions, slide, runby. Building has emergency generator, determine if elevators operate on generator, if so, test. 2/22/2024