Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 No No 2.18.5.3 - A rope data tag is required on the governor rope. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 No No 2.21.1.2 - Secure counterweights in the frame. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.1 No No 2.29.1(g) - Label the crosshead with the elevator number. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.27 - Crosshead data plate 2.20.2 No No A rope data tag is required on the suspension ropes. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No Adjust the door restrictor for proper operation. 10/19/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No The fire extinguisher is expired. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room. 1/21/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) No No The hoist ropes need replacing. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational (3rd Notice). Per Chief Inspector Gus Guadamuz, 14 days to fix phones or individual units will start being taken out of service. 8/27/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 12/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. Violation originally cited on 10/20/22 and still not corrected. Violations shall be corrected within 14 days or elevator will be red tagged and locked out of service. 3/11/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems Yes No Tighten the upthrust on the 9th floor hoistway door. 10/19/2020
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No A clear path shall be provided to the machine room. Remove paint, supplies, etc. and make a clear path to machine room. 1/21/2026
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No Handrails shall be provided on all nonaccess walls.