MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher is expired. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)1 A clear path shall be provided to the machine room. Remove paint, supplies, etc. and make a clear path to machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational (3rd Notice). Per Chief Inspector Gus Guadamuz, 14 days to fix phones or individual units will start being taken out of service. 8/27/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 10/20/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. (2nd Notice) 12/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. Violation originally cited on 10/20/22 and still not corrected. Violations shall be corrected within 14 days or elevator will be red tagged and locked out of service. 3/11/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Test is incomplete. The following testing items remain: Governor pull out/pull thru, tach governor, tag all devices, and test counterweight buffer. 10/20/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) Duct covers are missing from the top of the hoistway. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) 8.6.4.3 - Metal hoistway door fire gib is missing on floors 12 & 14. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 2.18.5.3 - A rope data tag is required on the governor rope. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) A rope data tag is required on the suspension ropes. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) The hoist ropes need replacing. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) Replace the hoist ropes. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 2.21.1.2 - Secure the counterweights in the frame. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.6 - Final and emergency terminal stopping devices 8.11.2.1.3(h) x x Top final limit shall work before the buffer is compressed. Unit Red-Tagged. 1/28/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.1 2.29.1(g) - Label the crosshead with the elevator number. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.11.2.3.6 x The counterweight buffer switch shall work. 1/28/2019