Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.6 - Final and emergency terminal stopping devices 8.11.2.1.3(h) Yes Yes Top final limit shall work before the buffer is compressed. Unit Red-Tagged. 1/28/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.11.2.3.6 Yes No The counterweight buffer switch shall work. 1/28/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) No No The hoist ropes need replacing. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) No No Replace the hoist ropes. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) No No 8.6.4.3 - Metal hoistway door fire gib is missing on floors 12 & 14. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) No No A rope data tag is required on the suspension ropes. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 No No 2.18.5.3 - A rope data tag is required on the governor rope. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 No No 2.21.1.2 - Secure the counterweights in the frame. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.1 No No 2.29.1(g) - Label the crosshead with the elevator number. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) No No Duct covers are missing from the top of the hoistway. 1/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 10/20/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No Test is incomplete. The following testing items remain: Governor pull out/pull thru, tach governor, tag all devices, and test counterweight buffer. 10/20/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. (2nd Notice) 12/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. Violation originally cited on 10/20/22 and still not corrected. Violations shall be corrected within 14 days or elevator will be red tagged and locked out of service. 3/11/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational (3rd Notice). Per Chief Inspector Gus Guadamuz, 14 days to fix phones or individual units will start being taken out of service. 8/27/2024
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No Handrails shall be provided on all nonaccess walls.
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No The car enclosure shall be so constructed that removable portions cannot be dismantled from within th car.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No The fire extinguisher is expired. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room. 1/21/2026
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No A clear path shall be provided to the machine room. Remove paint, supplies, etc. and make a clear path to machine room. 1/21/2026