ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
|
|
The hoist ropes need replacing.
|
1/4/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
|
|
Replace the hoist ropes.
|
1/4/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
|
|
8.6.4.3 - Metal hoistway door fire gib is missing on floors 12 & 14.
|
1/4/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
|
|
A rope data tag is required on the suspension ropes.
|
1/4/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
2.18.5
|
|
|
2.18.5.3 - A rope data tag is required on the governor rope.
|
1/4/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
2.21
|
|
|
2.21.1.2 - Secure the counterweights in the frame.
|
1/4/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.1
|
|
|
2.29.1(g) - Label the crosshead with the elevator number.
|
1/4/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
8.11.2.1.3(r)
|
|
|
Duct covers are missing from the top of the hoistway.
|
1/4/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher is expired. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
A clear path shall be provided to the machine room. Remove paint, supplies, etc. and make a clear path to machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational (3rd Notice). Per Chief Inspector Gus Guadamuz, 14 days to fix phones or individual units will start being taken out of service.
|
8/27/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.6 - Final and emergency terminal stopping devices
|
8.11.2.1.3(h)
|
x
|
x
|
Top final limit shall work before the buffer is compressed. Unit Red-Tagged.
|
1/28/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
8.11.2.3.6
|
x
|
|
The counterweight buffer switch shall work.
|
1/28/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
10/20/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Test is incomplete. The following testing items remain: Governor pull out/pull thru, tach governor, tag all devices, and test counterweight buffer.
|
10/20/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational. (2nd Notice)
|
12/14/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational. Violation originally cited on 10/20/22 and still not corrected. Violations shall be corrected within 14 days or elevator will be red tagged and locked out of service.
|
3/11/2024
|