ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Machine room ceiling insulation is falling down and laying on pump and floor. Clean and take corrective action.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.4 Protection of Light Bulbs and Tubes
|
|
|
Cab light shall be guarded against breakage.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Fire service shall work as designed.
|
4/9/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
4/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.14 - Ventilation
|
8.11.2.1.1(n)
|
|
|
The fan guard is missing in the cab.
|
5/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
|
Fire service phase 1 and 2 shall be tested. Fire Service key was not available at this time.
|
9/27/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency lighting inside car shall work.
|
9/27/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Electric eye is not working.
|
9/27/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4 Access to Pit
|
x
|
|
Pit machine space door shall be self-closing and self-locking. The lock is broken.
|
9/27/2024
|