Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Ran into issues during testing. The following items shall be tested to complete the annual inspection and category 5 test: Testing of lights, alarm, and phone with 110v removed, Governor pull out/pull thru, governor electrical switch and jaw, slide, oil buffer test, 125 % weight test. 1/18/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Cab floor to sill to hall floor shall be level and even. Currently, the cab and hall flooring are +1/2" above sill heights creating a tripping hazard. Repair/replace as needed.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work with and without main power. 8/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hanger track.
MO Minimum : Elevators (H) - Machine Rooms (H)1 Roof to machine room stairs are deteriorated, handrail has broken loose from concrete creating an unsafe condition. Repair/replace as needed to provide safe access.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room windows are broken and missing panes.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing, self-locking, and operable from the interior space without the use of a key.
MO Minimum : Elevators (H) - Machine Rooms (H)8 4 x 4 electrical box in machine room needs to have wiring inside box and cover installed.
MO Minimum : Elevators (H) - Machine Rooms (H)8 The hoist motor and motor generator sets shall have junction box covers in place. 2/1/2021
MO Minimum : Elevators (I) - Pits (I)1 The pit needs to be cleaned.
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)4 x x The safety drum rope shall not pullout more than 36". Currently pulls out 55". Red Tag Issued 8/3/2023
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)4 x x The safety drum rope shall not pullout more than 36". Currently pulls out 55". 9/8/2023
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)5 x x SOS switch will not reset. Take corrective action as needed. 9/8/2023
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)5 x x SOS switch will not reset. Take corrective action as needed. 8/3/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate There is no state operating certificate in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Suspension means shall have proper data tag.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The correct elevator number shall be displayed on the crosshead.
conversion conversion conversion - reinspect x Wind up car safety rope shall be made of a non-corrosive material. 12/4/2018