Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 Hoistway junction box at 6th floor shall have a cover. 2/1/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In cab emergency telephone shall work. 1/24/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current ABC fire extinguisher shall be provided in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm bell is not functional.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Auxiliary lighting is not functional.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm bell is not functional. 7/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Auxiliary lighting is not functional. 7/18/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Broken windows in machine room shall be repaired.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing & self-locking and open from the interior without the use of a key.
MO Minimum : Elevators (H) - Machine Rooms (H)8 Hoist motors and generators shall have junction box covers in place.
MO Minimum : Elevators (H) - Machine Rooms (H)1 x Stairs to machine room are deteriorated and handrail is loose and a section at the landing is completely missing, creating a fall hazard. Repair/replace as needed to create a safe condition.
MO Minimum : Elevators (H) - Machine Rooms (H)8 The hoist motor and motor generator sets shall have junction box covers in place. 2/1/2021
MO Minimum : Elevators (H) - Machine Rooms (H)1 x Stairs to machine room are deteriorated and handrail is loose and a section at the landing is completely missing, creating a fall hazard. Repair/replace as needed to create a safe condition. 7/18/2025
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire service not operating correctly. Elevator Red Tagged. 4/29/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service and door pressure shall be tested after SOS switch repaired to finish inspection.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Fire service panel at first floor is showing "trouble" error but smoke detectors are powered. Fire panel is completely non-functioning at this time. Elevator Red Tagged
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Safety operator (SOS) broke during testing and needs to be repaired. Elevator Red Tagged.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x The safety rope shall be made of a non-corrosive material. 1/18/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unable to complete the annual inspection and category 5 test. The following items shall be tested to complete the inspection: Testing of emergency light, alarm, and bell with 110v removed, door pressure, slide, and oil buffer testing. 1/18/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The 2024 annual inspection still needs to be completed. All testing items remain. 4/29/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service has been tested and red tag removed. The 2024 annual still needs to be completed. 6/17/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Fire service panel at first floor is showing "trouble" error but smoke detectors are powered. Panel shall be repaired within 14 days or both elevators may be removed from service. 7/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service and door pressure shall be tested after SOS switch repaired to finish inspection. 7/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Safety operator (SOS) broke during testing and needs to be repaired. 7/18/2025
conversion conversion conversion - reinspect x Wind up car safety rope shall be made of a non-corrosive material. 12/4/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current operating certificate shall be posted in the machine room in a non-combustible frame with a clear protective plate over it.