A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Auxiliary power lowering unit (emergency rescue unit) does not work, needs repair. Re-inspection required
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
No floor numbers on back of hoistway doors. 3.9.1(a)
|
1/17/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need a maintenance control plan and post on controller
|
11/6/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
11/6/2020
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Hydraulic pump electric motor is stalling before the relief valve opens. Repair/replace electric pump motor and perform relief valve test. REINSPECT REQUIRED
|
3/22/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperative emergency phone. Re-inspection required
|
11/4/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work correctly.
|
1/11/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
x
|
|
Auxiliary power lowering unit (emergency rescue unit) does not work, needs repaired. Re-inspection required
|
7/18/2024
|