Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary power lowering unit (emergency rescue unit) does not work, needs repair. Re-inspection required
MO Minimum : Elevators (A) - Hoistways (A)1 No floor numbers on back of hoistway doors. 3.9.1(a) 1/17/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need a maintenance control plan and post on controller 11/6/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 11/6/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Hydraulic pump electric motor is stalling before the relief valve opens. Repair/replace electric pump motor and perform relief valve test. REINSPECT REQUIRED 3/22/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone. Re-inspection required 11/4/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide existing phone to work correctly. 1/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x Auxiliary power lowering unit (emergency rescue unit) does not work, needs repaired. Re-inspection required 7/18/2024