Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide written maintenance control program on site.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 2/10/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x This unit has an OSV that is due for testing this year. Full load Cat 5 testing needs to be performed. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete, need to perform the following tests to complete inspection: Fire service testing. Re-inspection required