Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No The emergency stop switch in the elevator would not deactivate intermittently, replacement of the stop switch is required. 7/31/2018
conversion conversion n/a No No The machine room lighting fixture was not operational on the day of inspection. Repair the lighting fixture for proper illumination for maintenance and emergency personnel. 7/31/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 1/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Fire service Phase I key switch bezel in main lobby is un-readable, replace same 1/16/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 No No Gap between door and COP needs to be addressed. 1/16/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 1/16/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 1/16/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No One of the 2 buttons for the alarm bell does not work, needs repaired. Re-inspection required 12/4/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Category 5 test must be doneFire service must be testedEmergency light bell and phone must be tested 7/1/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Cat 5 full load testing is overdue. Perform required testing as noted in original inspection. Re-inspection required 12/21/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No 5 year inspection was started, but not completed. Need to preform full load full speed car safeties, 125% brake test, full load full speed car buffer, counterweight buffer, governor rope pull out, governor rope pull thru. Re-inspection required within 90 days 2/13/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Cat 5 testing incomplete - governor trip speeds need tested and car set on safeties to complete cat 5 testing 2/28/2024
MO Minimum : Elevators (F) - Electrical Switches (F)1 Yes No Stop switch alarm inoperative. Repair 1/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency light inoperative. 12/9/2020