MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Category 5 test must be doneFire service must be testedEmergency light bell and phone must be tested
|
7/1/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Cat 5 full load testing is overdue. Perform required testing as noted in original inspection. Re-inspection required
|
12/21/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5 year inspection was started, but not completed. Need to preform full load full speed car safeties, 125% brake test, full load full speed car buffer, counterweight buffer, governor rope pull out, governor rope pull thru. Re-inspection required within 90 days
|
2/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Cat 5 testing incomplete - governor trip speeds need tested and car set on safeties to complete cat 5 testing
|
2/28/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)4
|
|
|
Gap between door and COP needs to be addressed.
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
Stop switch alarm inoperative. Repair
|
1/23/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light inoperative.
|
12/9/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Fire service Phase I key switch bezel in main lobby is un-readable, replace same
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
One of the 2 buttons for the alarm bell does not work, needs repaired. Re-inspection required
|
12/4/2024
|
conversion
|
conversion
|
n/a
|
|
|
The emergency stop switch in the elevator would not deactivate intermittently, replacement of the stop switch is required.
|
7/31/2018
|
conversion
|
conversion
|
n/a
|
|
|
The machine room lighting fixture was not operational on the day of inspection. Repair the lighting fixture for proper illumination for maintenance and emergency personnel.
|
7/31/2018
|