MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the currents state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
One of the 2 buttons for the alarm bell does not work, needs repaired. Re-inspection required
|
12/4/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5 year inspection was started, but not completed. Need to preform full load full speed car safeties, 125% brake test, full load full speed car buffer, counterweight buffer, governor rope pull out, governor rope pull thru. Re-inspection required within 90 days
|
2/28/2024
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
Stop switch alarm inoperative. Repair
|
1/23/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Cat 5 full load test is overdue. Perform required testing. Re-inspection is required
|
12/22/2022
|