MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Replace sheave liners.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Replace drywall in hoistway that has been cut out on 3rd floor.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Both alarm bell buttons are not working correctly, need to be replaced. Re-inspection required
|
12/4/2024
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
Cab stop switch alarm inoperative. Repair
|
1/23/2020
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
2.18.9
|
x
|
|
Overspeed governor was replaced at an earlier time and was recalibrated, but the data plate was not changed to reflect changed. Replace plate with one that has correct information. Re-inspection required, but can be performed at a time of completion of 5 yr testing
|
2/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5 year inspection was started, but not completed. Need to preform full load full speed car safeties, 125% brake test, full load full speed car buffer, counterweight buffer, governor rope pull out, governor rope pull thru. Re-inspection required within 90 days
|
2/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Cat 5 testing incomplete - governor trip speeds need tested and car set on safeties to complete cat 5 testing
|
2/28/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Phase II does not work in car. Repair within ten (10) days or red tag unit.
|
7/1/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Cat 5 full load testing is overdue. Perform required testing. Re-inspection required
|
12/22/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Hands free cab phone inoperative. Repair - possible lost signal.
|
12/9/2020
|