Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x 5 year inspection was started, but not completed. Need to preform full load full speed car safeties, 125% brake test, full load full speed car buffer, counterweight buffer, governor rope pull out, governor rope pull thru. Re-inspection required within 90 days 2/13/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Both alarm bell buttons are not working correctly, need to be replaced. Re-inspection required 12/4/2024
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Cab stop switch alarm inoperative. Repair 1/23/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Cat 5 full load testing is overdue. Perform required testing. Re-inspection required 12/22/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Cat 5 testing incomplete - governor trip speeds need tested and car set on safeties to complete cat 5 testing 2/28/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Hands free cab phone inoperative. Repair - possible lost signal. 12/9/2020
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 2.18.9 x Overspeed governor was replaced at an earlier time and was recalibrated, but the data plate was not changed to reflect changed. Replace plate with one that has correct information. Re-inspection required, but can be performed at a time of completion of 5 yr testing 2/13/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase II does not work in car. Repair within ten (10) days or red tag unit. 7/1/2022
MO Minimum : Elevators (A) - Hoistways (A)13 Replace drywall in hoistway that has been cut out on 3rd floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace sheave liners.