Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service, 110V, and door pressure need to be tested. 3/15/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes are undersized. Need to be replaced within sixty (60) days. 3/15/2021
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)5 x x Tape selector broke off and ended up in the pit during counterweight buffer test. Red tagged elevator. 3/15/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The elevator tape reader electrical box cover is missing and shall be replaced. 1/19/2022
conversion conversion n/a The car door reopening device was working intermittently on the day of inspection. Repair or replace the reopening device for passenger safety. 7/31/2018