Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) Yes No Counterweights strike buffer with car at top floor, minimum runby is less than 6". Hoist ropes need to be shortened to attain 6-12" measurement 12/14/2023
MO Minimum : Elevators (A) - Hoistways (A)9 No No Provide key(s) for emergency stop switch in car 6/13/2024
MO Minimum : Elevators (A) - Hoistways (A)9 No No Provide keys for emergency stop switch in car 6/13/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Inspection is incomplete due to the elevator being stuck on the safeties. The following items still need to be tested: Governor pull out/thru, governor switch/jaw, slide, unintended up, door pressure, phone, alarm, emergency light & fire service. 5/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes Yes Unit was red tagged due to severe rusting of the counterweight buffer and channel, rail clips at the bottom of the car and counterweights rails, and the brackets/feet for all four rails. 2/9/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No None of the annual inspection was done due to red tag and shall be completed. RM 2/9/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Complete annual inspection still needed. 3/24/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Car Buffer support channels appear severely damaged by rust. Replacement of these C-Channels is required or provide engineer stamped documentation of integrity
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Emergency light shall work. 4/16/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Emergency alarm bell shall work. 4/16/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No One suspension rope is missing a shackle end cable clip. 11/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Provide on-site maintenance control program. 11/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Maintenance records shall be kept on site. 8/10/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Phone in car works, but dials 911. Reprogram to call non emergency number with 24/7 support. 11/20/2023