MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
No
|
No
|
Plastic covers shall be placed on the car light bulbs to protect people from glass in case of breakage or replace to plastic ceiling tiles
|
5/22/2023
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current State operating certificate shall be displayed in the machine room
|
8/7/2026
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
Yes
|
No
|
Fire service operation still needs to be tested.
|
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
Yes
|
No
|
Car door restrictor not working.
|
4/17/2019
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
Yes
|
No
|
Car door restrictor not working.
|
8/26/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
Yes
|
No
|
Door restrictor shall be made operable
|
5/22/2023
|
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
Yes
|
Yes
|
The safeties are not working properly. Elevator Red Tagged.
|
8/14/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Safeties shall be tested with full load.
|
8/14/2024
|
|
A17.1-1996 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
1001.2(e)(10)
|
Yes
|
Yes
|
safety rope pullout exceeded the distance allowed
|
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
Yes
|
Yes
|
Hoist ropes must be replaced as they have significant rouging and rope diameter is below the minimum code required.
|
|