Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all non elevator storage from the machine room 5/23/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No The emergency lowering device (ERU) shall be operational. 6/21/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency alarm bell shall be operational on auxiliary power. 6/21/2021
A17.1-1996 : Elevators 1.7 - Car door or gate 1001.2(a)(7) No No Correct source of noise from car door. 6/4/2019
A17.1-1996 : Elevators 1.4 - Sills and car floor 110.11a No No Secure carpet at 2nd floor elevator entrance. Tripping hazard. 6/13/2025
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The in car emergency lighting shall be operational. 6/21/2021
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 No No Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. 6/21/2021
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Repair emergency battery lowering unit. 9/19/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM 6/13/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Document routine maintenance in the maintenance control program 5/23/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Service fire extinguisher in the machine room 6/28/2024
A17.1-2016 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.11.1 Firefighters’ Emergency Operation No No PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM 6/13/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service and document on log in machine room 6/28/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 5/23/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 6/21/2021