Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Clena excess kint from rails & pit (fire hazard) 5/25/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform mnothly fire service test and document on log in the machine room 6/28/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test and document on log in machine room 5/25/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 5/25/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/25/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 5/25/2021
conversion conversion n/a Fire Service light and buzzer inoperative, repair item 7/9/2018